                更新時間:2021-05-30 點擊量:1209
                  自檢方式為消防給水系統中消防泵的日常檢測提供了一種方法。在消防泵自檢中,不僅可防止消防泵的銹蝕卡死,還可對電機過載、短路、過壓、缺相、欠壓、過熱等作出報警。消防泵的自檢對提高系統的管理水平不失為一種技術進步。
                  在消防泵自檢方式中,均能體現出自檢對消防泵的維護作用,但低速自檢方式僅運行了消防泵啟動中的一個初級階段,不能*反映出今后消防泵實際運行的工況。此外,消防泵自檢的結果反饋到消防控制中心后,需要人工作出進一步的判斷。故消防泵自檢方式不能*代替人工對消防泵的維護管理。
                  自檢方式的分析
                  常速自檢方式在一定的時間內模擬了消防給水的實際工況。其檢測的是消防泵啟動、正常運行的全過程。而在管路設計上需作改進。最重要的是要防止旁通管路上的電磁閥故障,必須做到在自檢時打開,自檢完成后及時關閉。
                  低速自檢方式不需對消防泵的管路作改動,但其檢測的僅是消防泵正常工況中的一個階段。消防泵可分為直接啟動和間接啟動,功率較大的需要間接啟動。而間接啟動有Y/△降壓啟動、自耦降壓啟動、軟啟動器啟動等方式。在消防泵運行中,軟啟動器啟動僅是消防泵運行的一個前期階段,其后才是正常的運行。變頻方法也未能運行到工頻階段。但對于防止消防泵的銹蝕,低速自檢方式還是有一定的作用。相對而言,它具有低頻驅動、低速轉動、設備低功耗運行的特點。