              1. 網站首頁技術中心 > 消火栓噴淋泵的啟動方式有何不同
                產品中心

                Product center

                消火栓噴淋泵的啟動方式有何不同

                更新時間:2015-11-10 點擊量:2259
                消火栓噴淋泵的啟動方式有何不同
                  消火栓泵與噴淋泵的啟動方式
                  消防控制室與消火栓動作按鈕啟動關系與消火栓泵的啟動形式有關。消火栓泵的啟動方式一般分為兩種,*種啟動方式是在總線制聯控方式下,消火栓動作按鈕的起動可通過設在消火栓旁的聯動接口模塊將其要求的啟動信號送至消防控制室控制臺,再從此處輸出使消火栓啟動的開關量觸點。第二種起動方式,是直接將消火栓動作按鈕的開關量觸點輸出到消火栓泵啟動箱。
                  這兩種啟動方式在實際設計中都可以運用,前一種方式接線省,但需在總線制下,對消火栓聯動模塊進行地址編碼編程來達到監測大量消火栓的目的。
                  后一種啟動方式簡單可靠,但還需要把消火栓動作信號返給消防控制室。設計者在具體設計中可根據實際工程規模大小來選用,工程規模大、建筑形式復雜可采用前一種啟動方式,規模小可采用后一種啟動方式。
                  噴淋泵的自啟動是通過各保護區的管網噴嘴玻璃球高溫下爆碎,引起管網水流流動,從而聯動報警閥壓力開關動作,達到自啟動噴淋泵的目的。通過水流指示器聯動模塊或報警閥壓力開關引線至控制室,消防控制室能準確反映其動作信號,同時控制室應能直接控制噴淋泵啟停。
                  消火栓噴淋泵是一種高性能消防泵,分別有單吸單級和單吸多級分段式二種,供輸送不含固體顆粒的清水及物理化學性質類似于水的液體之用。